| Trip characteristic | B curve | Magnetic instantaneous trip at approximately 3–5 times the rated current (In) under IEC 60898-1 conventions. | Resistive lighting, heating loads, and long cable runs with low inrush current. | Confirm that normal startup current will not cause unwanted tripping. |
| Trip characteristic | C curve | Magnetic instantaneous trip at approximately 5–10 times In under IEC 60898-1 conventions. | General-purpose branch circuits, small motors, pumps, transformers, and moderate inrush loads. | Check motor starting current and the available fault current before selection. |
| Trip characteristic | D curve | Magnetic instantaneous trip at approximately 10–20 times In under IEC 60898-1 conventions. | High-inrush equipment such as larger motors, transformers, and certain power supplies. | Use only when the system can deliver sufficient fault current for reliable instantaneous operation. |
| Trip characteristic | Adjustable electronic or magnetic trip | Long-time, short-time, instantaneous, and sometimes ground-fault settings may be adjustable. | Industrial branch circuits requiring coordination, selectivity, or higher ratings. | Settings must be coordinated with cable ampacity, downstream devices, and the prospective short-circuit current. |
| Rated current | In selected to protect the conductor | Common miniature circuit breaker ratings include 6 A, 10 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, and 63 A, depending on the product standard. | All branch circuits after applying the equipment load and installation conditions. | Do not size the breaker above the permitted ampacity of the connected conductors unless the governing code allows a specific exception. |
| Number of poles | 1 pole | Protects one live conductor in a single-phase circuit; neutral switching is normally not included. | Single-pole line-to-neutral circuits where local wiring rules permit unswitched neutral conductors. | Verify whether the local code requires simultaneous disconnection of all ungrounded conductors. |
| Number of poles | 1P+N | One protected live pole plus one neutral pole; neutral switching may be provided without overcurrent protection on the neutral pole. | Single-phase circuits where isolation of the neutral is required or preferred. | Confirm whether the neutral pole is switched only or also protected, and check the approved wiring arrangement. |
| Number of poles | 2 poles | Simultaneous operation of two poles; both poles may be overcurrent-protected depending on the design. | Line-to-line circuits, two-wire circuits requiring common disconnection, or selected single-phase systems. | Check whether both conductors are live and whether the device is rated for the system voltage between them. |
| Number of poles | 3 poles | Protects and disconnects the three phase conductors of a three-phase circuit. | Three-phase motors, heating equipment, and balanced three-phase loads without a switched neutral requirement. | Verify phase-to-phase voltage, phase sequence requirements, and whether the neutral must also be disconnected. |
| Number of poles | 3P+N or 4 poles | Three phase conductors plus a switched neutral; neutral protection depends on the system design and applicable rules. | Three-phase, four-wire systems where complete circuit isolation is required. | Confirm neutral switching requirements, neutral sizing, and compatibility with residual-current protection. |
| Rated voltage | System-specific voltage rating | Common low-voltage systems include approximately 120 V, 230 V, 400 V, and 415 V, but actual values vary by country and installation. | Single-phase and three-phase distribution systems worldwide. | The breaker voltage rating must be equal to or greater than the maximum system voltage for the intended pole arrangement. |
| Frequency | 50 Hz, 60 Hz, or 50/60 Hz | Many low-voltage breakers are marked for 50/60 Hz, while some products have specific frequency limitations. | International installations with different utility frequencies. | Read the device marking and technical documentation before exporting or installing. |
| Interrupting capacity | Short-circuit rating selected for the installation | Typical miniature breaker values may include 4.5 kA, 6 kA, or 10 kA; higher-capacity devices are available for industrial systems. | Residential, commercial, and industrial branch circuits with different fault levels. | The interrupting rating must be at least equal to the prospective short-circuit current at the installation point. |
| Product standard | IEC-based or North American-based construction | IEC 60898-1 commonly covers household and similar-use circuit breakers; IEC 60947-2 covers circuit breakers for broader industrial applications. Other markets may use different national requirements. | Export projects, panel building, residential installations, and industrial control systems. | Do not assume that IEC B, C, or D curves are directly interchangeable with trip classifications used under other standards. |
| Additional protection | Residual-current or ground-fault protection | Provides protection against leakage or ground-fault conditions; it is not a substitute for overcurrent protection unless the device is specifically combined for both functions. | Wet areas, socket circuits, outdoor circuits, and installations requiring additional personnel or equipment protection. | Select the correct residual-current sensitivity, time delay, waveform type, pole configuration, and local code compliance. |
| Coordination | Selectivity and backup protection | The upstream and downstream protective devices should be evaluated together for overload, short-circuit, and time-current coordination. | Facilities where only the faulted branch should disconnect or where continuity of service is important. | Use manufacturer coordination tables or a verified protection study where required by the project. |